Redundant design for power availability and site maintainability
Static Transfer System from 200 to 1600 A
Advantages
STATYS provides
- High reliability - internal redundant design. Flexibility and adaptability to various types of applications.
 - Compact design: saves up to 40% of valuable space.
 - Operational security and ease of use Remote data access in real time and from any location.
 - Full support and service.
 
High availability
- Complete separation of both sources and the related distribution systems.
 - Dual source redundancy supplies the load choosing the best source quality ensuring continuity
 - No-break transfer of the loads.
 - Distributed STS for load separation avoiding mutual disturbances.
 - Full internal redundant design and failure management.
 - Separation of main functions to prevent internal fault propagation.
 - Neutral loss detection on both sources.
 
High flexibility
-  Suitable for all types of:
- applications and power supply systems,
- electrical environment conditions,
- load to protect. - Easy installation:
- for existing or new electrical plants,
- compact units,
- front access. - Available with or without neutral connection and with or without neutral pole switching.
 
Technical Data
| Size(A) | 
  | 
Electrical specifications
| Voltage | 208 - 220 / 380 - 415 / 440 V (±10%) | 
| Number of phases | 3ph+N or 3ph (+ PE) | 
| Frequency | 50 Hz or 60 Hz (±5 Hz (configurable)) | 
| Number of poles switching | 3 or 4-pole switching | 
| Neutral system | Compatible with all earthing systems | 
| Maintenance bypass | Interlocked and secured | 
| Overloads | 150% for 2 minutes - 110% for 60 minutes | 
| Efficiency | 99% | 
| Admissible power factor | No restrictions | 
Environment
| Operating ambient temperature | 0 - 40 °C | ||
| Relative humidity | 95% | ||
| Maximum altitude | 1000 m a.s.l. without derating | ||
| Cooling | Forced ventilation | ||
| Acoustic level at 1 m (ISO 3746) | 
  | 
Mechanical specifications
| Dimensions W x D x H | 
  | |||||
| Weight | 
  | |||||
| Degree of protection | IP20 | 
Standards
| Performance and safety | IEC 62310, IEC 60529, AS 62310, AS 60529 | 
| EMC | C2 category (IEC 62310-2, AS 62310.2) | 
| Protection class | CB or PC class | 
| Product declaration | CE, RCM (E2376) | 
(1) Depth does not include handles (+40 mm).