UPS protection for 19” rack integration
	Single/single phase UPS from 1.5 to 9 kVA

The solution for
- e.business
 - Server farms
 - Telecommunications
 - Medical
 - Computer networks
 
Advantages
A 19” rack solution
- The Mod-RM series enables the UPS and all the protected equipment (HUB, server, back-up units, etc.) to be integrated into a single 19” rack. These modules are prewired so that connection is easier, simplifying installation.
 
An adaptable system
- Mod-RM has been specifically designed for usage up to 9 kVA, which requires a combination of reliability and adaptability.
 - The free slots in each model enable the Mod-Power to be added to provide redundancy for the system or to increase the power.
 
Modular back-up time
- In the same way, the spaces available enable the Mod-Battery to be added to increase back-up time.
 
System upgrades
- Units bought separately (Mod-TW or Mod-RK) can be installed at a later date in a Mod-System, fulfilling your needs for modularity and redundancy.
 
Basic configurations
Expandable from 1.5 kVA to 6 kVA
| 
				 
 
  | 
			
				 
 
  | 
		
UPS and internal batteries
| 
				 
  | 
		
Technical Data
| Sn [VA] | 
				
  | 
		||
| Pn [W] | 
				
  | 
		||
| Input/Output | 1/1 | 
Input
| Rated voltage | 230V | 
| Voltage tolerance | ± 20 % (up to -30 % at 70 % nominal load)> | 
| Rated frequency | 50/60 Hz | 
| Frequency tolerance | ± 10 Hz | 
| Power factor | >0.99 | 
Output
| Rated voltage | 230 V (1ph + N) | 
| Voltage tolerance | ± 3% (adjustable 208/220/240 V) | 
| Rated frequency | 50/60 Hz | 
| Frequency tolerance | ± 2% (± 0.1% autonomous frequency) | 
| Overload | 110% for 1 minute, 130% for 10 seconds, 200% for 5 cycles | 
| Crest factor | 3/1 | 
Bypass
| Rated voltage | voltage selected | 
| Voltage tolerance | ± 15% | 
| Rated frequency | frequency selected | 
| Frequency tolerance | ± 2% | 
Efficiency
| Online mode @ 100 % of load | up to 91% | 
| Eco Mode | 97% | 
Environment
| Operating ambient temperature | from 0 °C up to +40 °C (from 15 °C to 25 °C for maximum battery life)  | 
		
| Relative humidity | 0% - 90% without condensation | 
| Maximum altitude | 1000 m without derating (max. 3000 m) | 
Mod-System
| Dimensions W x D x H | 3 slots 19" x 564 mm x 13U | 
| Weight with standard batteries | 57 kg (Mod-RM 315), 68 kg (Mod-RM 330) | 
| Degree of protection | IP20 | 
| Acoustic level at 1 m (ISO 3746) | <52 dBA | 
| Heat dissipation | 780W | 
| Input connections | terminals | 
| Output connections | terminals + 2 x IEC 320 C19 (16 A) | 
Standards
| Safety | IEC/EN 62040-1 | 
| EMC | IEC/EN 62040-2 | 
| Performance | IEC/EN 62040-3 | 
| Product declaration | CE | 